Air conditioner of Switch Cabinet
When the power consumption is 500W,
When the temperature difference between inside and outside is 15℃ and the surface area is
4.6㎡, 55.3Kcal/hr/㎡ x 4.6㎡ = 254Kcal/h
Temperature Differential (℃) | (kcal/h/㎡) | (BTU/h/㎡) |
---|---|---|
5 | 16.7 | 66.3 |
10 | 42.2 | 167.4 |
15 | 55.3 | 219.4 |
20 | 92.2 | 365.8 |
25 | 116.7 | 463.1 |
30 | 142.2 | 564.2 |
35 | 166.9 | 662.3 |
Control panel volume(W x H x D) - 800 x 1600 x 500,
[The method of calculating the surface area control panel(in the case of installing on the factory floor)]
: (0.8m x 1.6m x 2EA) + (1.6m x 0.5m x 2EA) + (0.8m x 0.5m x 1EA) = 4.6㎡
Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
---|---|---|
Transformer |
Rated Capacity
|
· Smaller in size leads to more Heat Loss Rate |
Voltage Control Unit | Approximately 10% of Rated Capacity | · Heat Loss |
Heavy Resistor, Fixed, Variable | Approximately 1/3 of Rated Capacity | - |
Constant-Voltage Switch | Approximately 10~15% of Rated Capacity | · Heat Loss |
UPS |
|
|
Switching Regulator | Approximately 30~55% of Rated Output |
|
Low-Tension Condenser | Approximately 0.2% of Rated Output | · Rated Capacity KVA. (100V, 60HZ,1KVA = 256.3㎌) |
Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
---|---|---|
AC SERVO AMP |
Rated Capacity
|
|
POWER UNIT | Approximately 3~5% of Rated Capacity |
|
Inverter | Approximately 3~5% of Rated Capacity |
|
Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
---|---|---|
Factory Computer | 1unit : Approximately 100~300W | - |
CRT | 1unit : Approximately 60~130W | · Vary according to size(inch) |
Flopppy Disc | 2unit of 3.5~5inches :20W | - |
Fixed Disc | 10~20 M byte 100 | · Power Supply |
Machinery Installed In Panel | Heat Loss-general Standards | Remarks |
---|---|---|
NFB, LEB |
(NBF) Rated Capacity
NBF+5W Approximately 20W(Leakage From Electronic Circuits) |
|
Electro-Magnetic Relay |
Rated Capacity
|
|
Thermal Relay |
Rated Capacity
|
· When Applying Maximum Static Capacity |
Relay | Approximately 5W | · When Applying Maximum Static Capacity |
Machinery Installed In Panel | Heat Loss-general Standards |
---|---|
Compact Relay | 1unit : Approximately 1~2W (NFB) |
SSC, SSR | Using Current X Approximately 1.6W |
Thermost at Meter |
|
Machinery Installed In Panel | Heat Loss-general Standards |
---|---|
Fan Moter |
|